MPUPC500 - 220S48 Distribution Network Automation Power - Specialized Power Supply Module

share
WeChat
Sina Weibo
QQ
QQ space
Douban
Baidu Post Bar
580.00
Series Power Supply Module Series for Electric Power
Model MPUPC500 - 220S48
Size 168*110*45
Input voltage 220VAC
Input voltage range 165 - 265VAC
Output voltage 48VDC
Output current 10.4A
13817961199
Consult Now
Detail


1. Performance characteristics and applicable scope

The MPUPC500-220S48 is a rechargeable modular power supply designed and manufactured by our company. This power supply features small size, high conversion efficiency, stable performance, primary and secondary side isolation, and high isolation strength. It adopts a modular metal casing, providing dust and moisture protection and strong anti-interference capabilities. The input and output terminals are easy to connect. This product has strong grid adaptability and can operate within a wide input voltage range. It also features output short-circuit protection.It features overvoltage protection and other safety functions. Additionally, this product has an intelligent charging function, capable of charging external 48V batteries, ensuring uninterrupted battery charging even during AC power outages.This power supply provides power to the load and features over-discharge protection; it displays the power status and includes a battery activation function, allowing for manual or automatic activation and maintenance via external signals. This power supply is suitable for power distribution network automation systems, intelligent power transformer substations, ring main units, and other industries requiring uninterrupted DC power supply with stringent requirements.

2. Technical parameters

Input characteristics


project

Test conditions

Minimum

Typical

Maximum

Input voltage range (Vac)

Output full load

165.0

220.0

265.0

Input voltage range (Vdc)

Output full load

200.0

300.0

375.0

Frequency (Hz)

Communication input

40

50

60


Output characteristics


project

Test conditions

Minimum

Typical

Maximum

Output voltage

Full range of inputs, output under normal typical load

53.2

53.5

53.8

AC power failure, battery powered

42.0

--

53.8

Output current (A)

Full range input, excluding charging current

0

5.6

--

Full range input, transientInrush current≤10S

0

--

13.0

Ripple noise (mVp-p)

Full range of inputs, output under normal typical load

--

--

400

Source effect (%)

Full range of inputs, output under normal typical load

--

--

±1.0

Load effect (%)

Typical input, with load varying between 10% and 100% of normal typical load.

--

--

±1.0

Battery float charge voltage (V)

 Full range input,I=4.0A,IB=0.01A

53.2

53.5

53.8

Battery constant current charging current (A)

Full range of inputs, typical load

1.00

1.20

1.40

Battery activation completion point (V)

Full range of inputs, output under normal typical load

44.0

45.0

46.0

Battery low voltage alarm point (V)

Full range of inputs, output under normal typical load

44.0

45.0

46.0

Battery discharge cut-off point (V)

Full range of inputs, output under normal typical load






42.0



43.0

44.0

Internal resistance of battery discharge circuit()

Discharge current15A

--

0.05

--

Maximum discharge current of battery(A)

Discharge time ≤30S

--

--

15

Activation contact contact time (s)

Remote activation start-up and exit

--

0.5

1.0

Remote battery ejection

--

0.5

1.0

Output overvoltage alarm(V)


59.0

60.0

61.0

Output short circuit protection

AC full range input

Turn off power output and cancel automatic restart.


General characteristics


project

Test conditions

Minimum

Typical

Maximum

Temperature coefficient (%/℃)

Full range of inputs, output under normal typical load

--

--

±0.02


Insulation resistance (M)


Test voltage

500VDC

Input to output

50

--

--

Input to chassis

50

--

--

Output housing

50

--

--

efficiency(%)

AC typical input and output under normal typical load, battery fully charged

--

84

--

Isolation voltage

Leakage current 5mA, power frequency 50Hz, no breakdown or flashover in 1 minute.

Input to output

1500Vac

Input to chassis

1500Vac

Output housing

500Vdc

External dimensions (mm)

168.0×110.0×45.0

Ambient temperature (°C)


-25

--

+65

Operating casing temperature (°C)


-25

--

+85

Storage temperature (°C)


-40

--

+105

Weight (kg)


--

1.5

--

Mean Time Between Failures (MTBF) (h)

Under room temperature conditions

80000

--

--

Note: When the ambient temperature exceeds 55°C, the module should be derated, or forced cooling methods such as air cooling or surface cooling should be adopted to ensure that the module shell temperature does not exceed 8°C.5℃.


3. Internal circuit principle of the power supply

Figure 1 Internal schematic diagram of the power supply

Figure 2 Internal isolation diagram of the power supply


4. Panel Description


Figure 3 Power Panel Description

1. Charging and operating indicator light 2. Battery discharge indicator light 3. Battery activation indicator light 4. Battery low voltage indicator light 5. Power failure (overvoltage) indicator light 6. Manual activation start button 7. Manual activation exit button 8. Manual battery insertion button 9. Manual battery eject button 10. Wiring terminals


5. Wiring Instructions

5.1Wiring diagram


Figure 4 Wiring diagram

Wiring Instructions: K1, K2, and K3 are relay contacts controlled by the user's CPU, etc. (contact capacity is not required, but optocouplers cannot be used as substitutes). The load is the user's normal load, and the battery is a 48V battery pack. The terminal block capacity is 300V/15A. See the usage instructions below for specific usage details.

5.2 Terminal Definition

Terminal number

Terminal Name

Definition


Terminal number

Terminal Name

Definition

1

ACL

AC input L phase

12

BG

Remote battery ejection

2

ON

Protective grounding

13

IN

Activation discharge external terminal

3

ACN

AC input N phase

14

VG

Remote control public contact

4

NC

No electrical connection

15

In-

Load output negative

5

VC

Alarm input is positive

16

In-

Load output negative

6

POK

Input power failure alarm output

17

In+

Load output positive

7

CAGE

Battery activation status output

18

In+

Load output positive

8

VL

Battery low voltage alarm output

19

B+

Battery connection positive

9

VH

Power failure alarm output

20

B+

Battery connection positive

10

HK

Remote activation start

21

B-

Battery connected to negative

11

HG

Remote activation exit

22

B-

Battery connected to negative


6. Instructions for Use

6.1 Power Status Indicator

Charging, green, battery charging indicator, illuminates when the battery is charging, and turns off when the battery is discharging or activating;

Discharge, red, battery discharge indicator, illuminates when the battery is discharging or activating, and turns off when the battery is charging or discharging is complete;

Activation indicator: Yellow. Light illuminates when the battery is activated; otherwise, it remains off.

Telephone
13818437569
QQ
783217385
WeChat
WeChat
ScanCode
WhatsApp
WhatsApp
ScanCode